• DocumentCode
    2163891
  • Title

    Simulation of electromagnetic transients in air insulated substation due to switch operation

  • Author

    Liang, Zhenguang ; Dou, Hui

  • Author_Institution
    Sch. of Electr. Eng., Shandong Univ., Jinan, China
  • fYear
    2009
  • fDate
    16-20 Sept. 2009
  • Firstpage
    43
  • Lastpage
    46
  • Abstract
    This paper describes electromagnetic transient in busbar of air insulted substation due to switch operation. Transmission line model and lumped parameter model are used to model high voltage bus. Interference of transient in busbar to secondary cable via CCVT is model by coupling capacitor. Simulation results show reflections of electromagnetic wave during propagation in busbar have influence on electromagnetic interference in substation.
  • Keywords
    busbars; electromagnetic coupling; electromagnetic interference; power system transients; substation insulation; switchgear; switching substations; CCVT; air insulated substation; air insulted substation busbar; busbar interference; coupling capacitor; electromagnetic interference; electromagnetic transient; secondary cable; switch operation; Couplings; Electromagnetic transients; Interference; Power cable insulation; Power cables; Power system transients; Substations; Switches; Transmission lines; Voltage; CCVT; Electromagnetic transient; busbar; coupling; substation; switch operation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environmental Electromagnetics, 2009. CEEM 2009. 5th Asia-Pacific Conference on
  • Conference_Location
    Xian
  • Print_ISBN
    978-1-4244-4344-4
  • Type

    conf

  • DOI
    10.1109/CEEM.2009.5304410
  • Filename
    5304410