Abstract
An original approach based on the method of experiment design in dynamic mode is proposed in order to study the effect of ageing factors on the paper/oil insulation in power transformers. The relevant calculations are described. The influence of the effects of each factor (temperature, oxygen pressure, catalyst and antioxidant) is quantified and discussed. Finally, a comparative study of three classes of antioxidant (phenols, amines and thiols) enabled the classification of these additives according to their reactivity and their efficiency with respect to the protection of mineral insulating oils and the depolymerization mechanisms of paper
Keywords
ageing; composite insulating materials; insulation testing; paper; power transformer insulation; power transformer testing; transformer oil; ageing factors; amines; antioxidant; catalyst; depolymerization mechanisms; oxygen pressure; paper/oil insulation; phenols; power transformers; protecting factors; temperature; thiols; Aging; Degradation; Inhibitors; Oil insulation; Oxidation; Petroleum; Power transformer insulation; Protection; Research and development; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1994., Proceedings of the 4th International Conference on
Conference_Location
Brisbane, Qld.
Print_ISBN
0-7803-1307-0
Type
conf
DOI
10.1109/ICPADM.1994.414136
Filename
414136
Link To Document