Title :
Lightning flashover rates of overhead distribution lines applying volt time curve from testing and IEEE Std.1410-2004
Author :
Thanasaksiri, T.
Author_Institution :
Dept. of Electr. Eng., ChiangMai Univ., Chiangmai, Thailand
Abstract :
This paper calculates the lightning flashover rates of 22 kV overhead distribution line. In order to calculate the backflashover rate (BFOR), the performance of line which related to the insulator backflashover has been modeled and analyzed using Electromagnetic Transient Program (EMTP). The shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) have been calculated follow equations given in IEEE std 1410-2004. Finally the total numbers of flashovers of line have been determined. The lightning flashovers rates of BFOR, SFFOR and IVFOR have also been compared with the data taken from the line outages recorder. From the system being studied shown that, the total numbers of flashovers from simulation and calculation is closed to the data from the line outage recorder.
Keywords :
EMTP; IEEE standards; flashover; lightning; power distribution lines; power overhead lines; EMTP; Electromagnetic Transient Program; IEEE Std. 1410-2004; backflashover rate; induced voltage flashover rate; insulator backflashover; lightning flashover rates; line outages recorder; overhead distribution lines; shielding failure flashover rate; volt time curve; voltage 22 V; Capacitors; EMTP; Equations; Flashover; Lightning; Mathematical model; Testing;
Conference_Titel :
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference on
Conference_Location :
Khon Kaen
Print_ISBN :
978-1-4577-0425-3
DOI :
10.1109/ECTICON.2011.5947926