DocumentCode :
2188397
Title :
Transformer winding diagnosis using comparison of transfer function coefficients
Author :
Bigdeli, Mehdi ; Vakilian, Mehdi ; Rahimpour, Ebrahim ; Azizian, Davood
Author_Institution :
Zanjan Branch, IDept. of Electr. Eng., Islamic Azad Univ., Zanjan, Iran
fYear :
2011
fDate :
17-19 May 2011
Firstpage :
681
Lastpage :
683
Abstract :
In this work, a new model of transformer winding is developed. The components in the model are determined by the geometric and electric data of the winding. Under different degrees of axial displacement and radial deformation in the winding, circuit parameters in the model will be changed and thus the character of the circuit will be influenced. After acquiring the model parameters in the intact and faulted cases, transfer function coefficients derived in model from nodal analysis. Then using introduce the new index based on coefficients we can specify the type and extent of penetration of the fault in the winding. Results presented demonstrate the potential of this method.
Keywords :
fault diagnosis; power transformers; transfer functions; transformer windings; transfer function coefficients; transformer winding diagnosis; Circuit faults; Coils; Electrical engineering; Integrated circuit modeling; Power transformers; Transfer functions; Windings; Axial Displacement; Radial Deformation; Transfer Function Coefficients; Transformer Winding;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference on
Conference_Location :
Khon Kaen
Print_ISBN :
978-1-4577-0425-3
Type :
conf
DOI :
10.1109/ECTICON.2011.5947931
Filename :
5947931
Link To Document :
بازگشت