• DocumentCode
    2188397
  • Title

    Transformer winding diagnosis using comparison of transfer function coefficients

  • Author

    Bigdeli, Mehdi ; Vakilian, Mehdi ; Rahimpour, Ebrahim ; Azizian, Davood

  • Author_Institution
    Zanjan Branch, IDept. of Electr. Eng., Islamic Azad Univ., Zanjan, Iran
  • fYear
    2011
  • fDate
    17-19 May 2011
  • Firstpage
    681
  • Lastpage
    683
  • Abstract
    In this work, a new model of transformer winding is developed. The components in the model are determined by the geometric and electric data of the winding. Under different degrees of axial displacement and radial deformation in the winding, circuit parameters in the model will be changed and thus the character of the circuit will be influenced. After acquiring the model parameters in the intact and faulted cases, transfer function coefficients derived in model from nodal analysis. Then using introduce the new index based on coefficients we can specify the type and extent of penetration of the fault in the winding. Results presented demonstrate the potential of this method.
  • Keywords
    fault diagnosis; power transformers; transfer functions; transformer windings; transfer function coefficients; transformer winding diagnosis; Circuit faults; Coils; Electrical engineering; Integrated circuit modeling; Power transformers; Transfer functions; Windings; Axial Displacement; Radial Deformation; Transfer Function Coefficients; Transformer Winding;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference on
  • Conference_Location
    Khon Kaen
  • Print_ISBN
    978-1-4577-0425-3
  • Type

    conf

  • DOI
    10.1109/ECTICON.2011.5947931
  • Filename
    5947931