DocumentCode :
2192107
Title :
Effect of short circuit current duration on the welding of closed contacts in vacuum
Author :
Slade, Paul G. ; Taylor, Erik D. ; Haskins, Richard E., Jr.
Author_Institution :
Eaton Electr., Horseheads, NY, USA
fYear :
2005
fDate :
26-28 Sept. 2005
Firstpage :
69
Lastpage :
74
Abstract :
High ac currents were passed through closed Cu-Cr (25 wt. %) contacts located in a vacuum ambient (pressure 10-4-10-3 Pa). The duration of the short circuit currents ranged from 1 second to 4 seconds. The contact welding was measured for a range of closed contact forces and current durations. The weld fracture strength was measured using a slowly rising opening force of 50 N/s. It was found that the contacts required a larger contact force to prevent welding if the current duration of 4 seconds was applied, than if a current of 1 second, 2 seconds and 3 seconds was applied. The data showed that there was a considerable scatter in the data for all conditions examined. It also showed that a weak weld could well follow a strong weld. A consideration of the transition to the steady state model of closed contact welding can explain the observed data.
Keywords :
chromium alloys; copper alloys; electric current; electrical contacts; short-circuit currents; vacuum circuit breakers; welding; 1 to 4 s; Cu-Cr; closed contact forces; closed contact welding; closed contacts; current durations; short circuit current; vacuum welding; weld fracture strength; Circuit breakers; Circuit testing; Contacts; Current measurement; Force measurement; Scattering; Short circuit currents; Steady-state; USA Councils; Welding;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Contacts, 2005. Proceedings of the Fifty-First IEEE Holm Conference on
Print_ISBN :
0-7803-9113-6
Type :
conf
DOI :
10.1109/HOLM.2005.1518225