Abstract
Characterization of five accuracy class 0.2 current transformers rated 600 A up to 2500 A is done by measurement of phase displacement and amplitude error as function of frequency and current. The test system is presented and the test procedure is described. The accuracy of test system voltage and current measurements is addressed and separate measurements on the transformer burden (load resistance) are carried using other test equipment. This enables an assessment of the test equipment measurement ability. Finally, measurements of the current error and phase displacement of five different current transformers with burden are carried out
Keywords
current transformers; displacement measurement; electric current measurement; power transformer testing; test equipment; voltage measurement; 20 Hz to 10 kHz; 600 to 2500 A; amplitude error measurement; current measurements; current transformers; phase displacement measurement; test system; voltage measurement; Current measurement; Current transformers; Displacement measurement; Frequency; Instruments; Phase measurement; Resistors; Signal generators; Testing; Time measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics, Electrical Drives, Automation and Motion, 2006. SPEEDAM 2006. International Symposium on
Conference_Location
Taormina
Print_ISBN
1-4244-0193-3
Type
conf
DOI
10.1109/SPEEDAM.2006.1649870
Filename
1649870
Link To Document