DocumentCode
2192844
Title
Measurement and study of arc characteristics of vacuum interrupter with high voltage and high capacity
Author
Li, Jin ; Jimei, Wang
Author_Institution
Dept. of Electr. Eng., Xi´´an Jiaotong Univ., China
Volume
1
fYear
1996
fDate
21-26 Jul 1996
Firstpage
266
Abstract
In this paper, the relationship between arc voltage and arc current, the influence of gap distance on arc noise and the relationship between arc voltage and main shield voltage are measured on a 63 kV/40 kA vacuum interrupter with a coil-axial magnetic field. The influence of breaking current on arc characteristics is also measured and the experimental results are analysed
Keywords
circuit-breaking arcs; electric breakdown; insulation testing; magnetic fields; switchgear testing; vacuum arcs; vacuum insulation; vacuum interrupters; 40 kA; 63 kV; arc characteristics; arc current; arc noise; arc voltage; breaking capacity; breaking current; coil-axial magnetic field; main shield voltage; vacuum interrupter; Anodes; Contacts; Current measurement; Electrons; Interrupters; Noise measurement; Switches; Switching circuits; Vacuum arcs; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location
Berkeley, CA
Print_ISBN
0-7803-2906-6
Type
conf
DOI
10.1109/DEIV.1996.545363