Transmission system parameters optimization - sensitivity analysis of secondary arc current and recovery voltage
Author
Tavares, Maria ; PORTELA, CARLOS
Author_Institution
State Univ. of Campinas, Brazil
fYear
2004
fDate
6-10 June 2004
Abstract
Summary form only given. This paper shows the importance of optimizing the transmission system parameters from its conception, considering altogether the relevant options and possibilities, in order to have the better cost-performance result. The presented results were obtained in the study of a real transmission system expansion, based on an 865 km long line. The single-phase auto-reclosing (SPAR) procedure was one of the aspects carefully studied, in order to assure adequate transmission reliability. The secondary arc current was mitigated through the traditional solution of using the neutral reactor on the existing shunt reactor banks, which permitted the reduction of the secondary arc current to acceptable values, assuring natural arc extinction and successful SPAR. The way of obtaining the optimized value for the neutral reactor and its implications on the system performance are important aspects, which are discussed in this paper.
Keywords
arcs (electric); optimisation; power transmission planning; power transmission reliability; sensitivity analysis; neutral reactor; real transmission system expansion; recovery voltage; secondary arc current; sensitivity analysis; shunt reactor bank; single-phase auto-reclosing; transmission reliability; transmission system parameters optimization; Inductors; Sensitivity analysis; Shunt (electrical); System performance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2004. IEEE
Print_ISBN
0-7803-8465-2
Type
conf
DOI
10.1109/PES.2004.1372824
Filename
1372824
Link To Document