• DocumentCode
    2194483
  • Title

    Real-time estimation of security from voltage collapse using synchronized phasor measurements

  • Author

    Khatib, A.R. ; Nuqui, R.F. ; Ingram, M.R. ; Phadke, A.G.

  • Author_Institution
    Dept. of Electr. Power & Energy, MTC, Cairo, Egypt
  • fYear
    2004
  • fDate
    6-10 June 2004
  • Firstpage
    582
  • Abstract
    We present a case study for estimating security from voltage collapse utilizing synchronized phasor measurements. Phasor measurement units (PMUs) provide the GPS time-synchronized voltage and current phasors that are transmitted to a central location where the system´s voltage security status is determined by a decision tree type algorithm. The decision tree architecture is designed using wide area measurements generated from off-line continuation power flow simulations. Accompanying system studies revealed that bus voltage angle differences and transmission line reactive flows constitute the best measurement attributes for determining voltage security. Decision trees allow update of voltage security with speed as fast as phasors are received at the central location.
  • Keywords
    decision trees; load flow; power engineering computing; power system dynamic stability; power system security; power transmission lines; GPS time-synchronized voltage; current phasors; decision tree type algorithm; off-line continuation power flow simulations; real-time estimation; synchronized phasor measurements; transmission line reactive flow; voltage collapse security; Decision trees; Global Positioning System; Load flow; Phasor measurement units; Power generation; Power system security; Power transmission lines; Transmission line measurements; Voltage; Wide area measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2004. IEEE
  • Print_ISBN
    0-7803-8465-2
  • Type

    conf

  • DOI
    10.1109/PES.2004.1372874
  • Filename
    1372874