Title :
Installation and equipment for the research of the electrical switching arc in advanced vacuum
Author :
Pavelescu, Dan ; Trusca, Vasile ; Nitu, Smaranda ; Dumitrescu, Gheorghe ; Maricaru, Mihai ; Zoita, Vasile
Author_Institution :
Politehnica Univ. of Bucharest, Romania
Abstract :
The paper presents some results obtained by the authors in the manufacture and use of equipment and adjacent measuring and diagnosis devices developed for the research of electrical switching arcs in vacuum. Tests were made for the current range 0.5-30 kA RMS and voltages between 200-1400 V. The evolution of currents and electrical switching voltages related to mechanical and vacuum breaking process parameters was recorded. Diagnosis measurements relatively to the diffuse or constricted state of the breaking electrical arc column were also performed. Research concerning the influence of the additional magnetic field upon the electrical switching arc in a vacuum have also been initiated
Keywords :
circuit-breaking arcs; electric breakdown; insulation testing; switchgear testing; switching; test equipment; vacuum arcs; vacuum breakdown; vacuum switches; 0.5 to 30 kA; 200 to 1400 V; breaking electrical arc column; diagnosis measurements; electrical switching arc; switching currents; switching voltages; vacuum breaking process parameters; vacuum switching devices; Circuit breakers; Circuit testing; Coaxial components; Electric variables measurement; Low voltage; Magnetic field measurement; Performance evaluation; Plasma measurements; Power supplies; Vacuum arcs;
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location :
Berkeley, CA
Print_ISBN :
0-7803-2906-6
DOI :
10.1109/DEIV.1996.545371