DocumentCode :
2198128
Title :
Fundamental studies on vacuum circuit breaker arc quenching limits using a synthetic test circuit
Author :
Betz, Thomas ; Koenig, Dieter
Author_Institution :
High Voltage Lab., Tech. Univ. Darmstadt, Germany
Volume :
1
fYear :
1996
fDate :
21-26 Jul 1996
Firstpage :
376
Abstract :
The aim of this work is to demonstrate the use of a synthetic test circuit with L-C resonant circuits for fundamental experimental work on vacuum circuit breakers (CB). Studies have been performed on a 36 kV-model CB at test currents of 5 and 10 kA rms aiming at separating the influence of different parameters of the transient recovery voltage (TRV) such as average rate of rise and peak value on the breaking capability. Furthermore the effect of the arcing time on the measured arc quenching limit is presented
Keywords :
circuit-breaking arcs; switchgear testing; vacuum arcs; vacuum circuit breakers; 10 kA; 36 kV; 5 kA; arcing time; average rate of rise; breaking capability; medium voltage circuit breaker; synthetic test circuit; test currents; transient recovery voltage; vacuum circuit breaker arc quenching limits; Circuit breakers; Circuit testing; Power system transients; RLC circuits; Switches; Switching circuits; Transient analysis; Tuned circuits; Vacuum arcs; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location :
Berkeley, CA
Print_ISBN :
0-7803-2906-6
Type :
conf
DOI :
10.1109/DEIV.1996.545385
Filename :
545385