DocumentCode :
2199619
Title :
Dynamic thermal modelling of power transformers
Author :
Susa, Dejan ; Lehtonen, Matti ; Nordman, H.
Author_Institution :
Helsinki Univ., Finland
fYear :
2004
fDate :
6-10 June 2004
Abstract :
Summary form only given. The aim of This work is to introduce hot-spot and top-oil temperature thermal models for more accurate temperature calculations during transient states, based on data received in a normal heat run test (i.e. the top oil in the tank of transformer and the average winding-to-average oil gradient). Oil viscosity changes and loss variation with temperature are taken into account. The new thermal models will be validated using experimental (fiber optic test) results obtained at varying load current on a 250 MVA-ONAF-cooled unit, a 400 MVA-ONAF-cooled unit and a 605 MVA-OFAF-cooled unit. The results are also compared with the IEEE-loading guide (1995) Annex G method.
Keywords :
optical fibre testing; power transformer testing; thermal analysis; transformer oil; viscosity; 250 MVA; 400 MVA; 605 MVA; OFAF; ONAF; dynamic thermal modelling; fiber optic test; heat run test; load current; loss variation; oil viscosity; power transformer; temperature calculations; transient states; Oil insulation; Optical fiber testing; Optical fibers; Optical losses; Petroleum; Power transformers; Temperature; Thermal loading; Viscosity;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2004. IEEE
Conference_Location :
Denver, CO
Print_ISBN :
0-7803-8465-2
Type :
conf
DOI :
10.1109/PES.2004.1373100
Filename :
1373100
Link To Document :
بازگشت