DocumentCode
2201234
Title
Analytical formulas of the electric field near a reinforced concrete pole of a MV line
Author
Desideri, Daniele ; Maschio, Alvise ; Poli, Enrico
Author_Institution
Department of Electrical Engineering, University of Padova via Gradenigo, 6/a, I-35131 Padova Italy
fYear
2007
fDate
24-28 Sept. 2007
Firstpage
353
Lastpage
356
Abstract
A medium voltage three-phase power line supported by reinforced concrete poles and with a pole-top-pin construction has been analyzed. An analytical model has been developed for the evaluation of the electric field, with a range of validity extending from the ground up to one quarter of the height of the poles supporting the line. The model consists in assuming that the charges on the overhead conductors are not affected by the presence of the poles, and in replacing the pole with a suitable charge distribution. In this way, new simple formulas for the estimation of the electric field that include the effect of the line supporting poles have been obtained and the analytical results have been experimentally validated.
Keywords
Analytical models; Concrete; Conductors; Electromagnetic compatibility; Frequency; Geometry; Medium voltage; Power overhead lines; Solid modeling; Wires;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2007. EMC Zurich 2007. 18th International Zurich Symposium on
Conference_Location
Munich, Germany
Print_ISBN
978-3-9523286-1-3
Electronic_ISBN
978-3-9523286-0-6
Type
conf
DOI
10.1109/EMCZUR.2007.4388268
Filename
4388268
Link To Document