DocumentCode
2201652
Title
Frequency dependent modeling of power transformers with ungrounded windings
Author
Gustavsen, Bjorn
Author_Institution
SINTEF Energy Res., Trondheim, Norway
fYear
2004
fDate
6-10 June 2004
Abstract
Summary form only given. A linear wide band transformer model for the purpose of simulation of electromagnetic transients has previously been developed by the author. The model was obtained via frequency domain measurements and rational approximation of the terminal admittance matrix Y. In the case of transformers with ungrounded windings, the model may produce erroneous results due to a near singular condition at low frequencies. This work shows that the problem can be overcome by explicit measurement and modeling of the zero sequence system. Blocks of Y which correspond to ungrounded windings are modified by removal of their zero sequence components. A new zero sequence system is obtained by dedicated measurements and the two functions are approximated with rational functions which are combined to produce the final model. Application to a wye-delta connected transformer demonstrates the validity of the approach.
Keywords
EMTP; electric admittance; frequency measurement; frequency-domain analysis; function approximation; matrix algebra; power transformers; rational functions; transformer windings; electromagnetic transient simulation; frequency dependent modeling; frequency domain measurements; linear wide band transformer model; power transformers; rational function approximation; terminal admittance matrix; ungrounded windings; wye-delta connected transformer; zero sequence system; Admittance measurement; Electromagnetic measurements; Electromagnetic modeling; Frequency dependence; Frequency domain analysis; Frequency measurement; Power transformers; Wideband;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2004. IEEE
Conference_Location
Denver, CO
Print_ISBN
0-7803-8465-2
Type
conf
DOI
10.1109/PES.2004.1373185
Filename
1373185
Link To Document