DocumentCode
2202087
Title
Orbit distortion due to the floor displacement in the light source building under climatic thermal stress
Author
Katsura, T. ; Kamiya, Y. ; Fujita, Y.
Author_Institution
Nat. Lab. for High Energy Phys., Tsukuba, Japan
fYear
1991
fDate
6-9 May 1991
Firstpage
2682
Abstract
Diurnal orbit drift in the storage ring was found. It resulted from floor displacement of the building distorted under climatic thermal stress. The building distortion was both simulated by using a computer model and measured with a leveling system. Both simulation and measurement gave a good evaluation of the floor displacement. The orbit drift calculated from the measured floor displacement agreed well with that actually measured with beam position monitors. As a consequence, it was decided to insulate the roof, which made the building distortion much smaller and the orbit drift minimal.<>
Keywords
particle beam diagnostics; storage rings; beam position monitors; building distortion; climatic thermal stress; computer model; diurnal drift; floor displacement; leveling system; light source building; orbit distortion; orbit drift; roof insulation; storage ring; Computational modeling; Computer simulation; Displacement measurement; Distortion measurement; Extraterrestrial measurements; Floors; Light sources; Position measurement; Storage rings; Thermal stresses;
fLanguage
English
Publisher
ieee
Conference_Titel
Particle Accelerator Conference, 1991. Accelerator Science and Technology., Conference Record of the 1991 IEEE
Conference_Location
San Francisco, CA, USA
Print_ISBN
0-7803-0135-8
Type
conf
DOI
10.1109/PAC.1991.165070
Filename
165070
Link To Document