Abstract :
Electrical tree inception tests have been carried out on different combinations of semiconductive screen (semicon) needle/XLPE insulation samples. The test programme has been designed so that it is possible to ascertain the main factors which promote or retard electrical tree inception. The results obtained have permitted predictions to be made of the most appropriate material combinations to give “good” and “poor” performance. These “good” and “poor” material combinations were then tested to verify the predictions. The results show that the experimentally measured performances agree with their predicted performances. Thus it can be concluded that by careful design and selection of semicon/XLPE combinations, samples with enhanced electrical treeing properties can be manufactured
Keywords :
XLPE insulation; partial discharges; power cable insulation; trees (electrical); XLPE insulation combinations; electrical tree inception; electrical treeing properties; power cables; semiconductive screens; Cable insulation; Dielectrics and electrical insulation; Laboratories; Materials testing; Needles; Organic materials; Performance evaluation; Stress; Trees - insulation; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
Conference_Location :
Arlington, VA
ISSN :
1089-084X
Print_ISBN :
0-7803-4927-X
Type :
conf
DOI :
10.1109/ELINSL.1998.694862
Filename :
694862
Link To Document :
بازگشت