• DocumentCode
    2208303
  • Title

    Parameters for Wind Caused Overhead Transmission Line Swing and Fault

  • Author

    Lihong, Long ; Yi, Hu ; Jinglu, Li ; Xiangjun, Zeng

  • Author_Institution
    Sch. of Electr. & Inf. Eng., Changsha Univ. of Sci. & Technol.
  • fYear
    2006
  • fDate
    14-17 Nov. 2006
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    It has been widely recognized that faults caused by windage yaw with a relatively high probability in recent years. Hence it is of great significance to investigate the characteristics of flashover caused by windage yaw and discuss the influences of windage yaw. A mathematical model of swing angle of conductor is developed in this paper, and the influence of three main parameters is fully discussed, including wind speed, wind pressure coefficient and wind height factor. The results can provide fundamental guideline for the design of line and tower, which will optimize the design and make the faults caused by wind decrease largely
  • Keywords
    flashover; poles and towers; power overhead lines; conductor swing angle; flashover; mathematical model; overhead transmission line; tower design; windage yaw faults; Conductors; Flashover; Guidelines; Insulation; Mathematical model; Power transmission lines; Rain; Sparks; Voltage; Wind speed;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    TENCON 2006. 2006 IEEE Region 10 Conference
  • Conference_Location
    Hong Kong
  • Print_ISBN
    1-4244-0548-3
  • Electronic_ISBN
    1-4244-0549-1
  • Type

    conf

  • DOI
    10.1109/TENCON.2006.343973
  • Filename
    4142563