Study of full scale UHV DC transmission line corona performance in corona cage
Author :
Wei Wang ; Li, Chengrong ; Liu, Yunpeng ; Luo, Bing ; Li, Xiaolin ; Jiang, Yitao ; An, Bing ; Wang, Yixu
Author_Institution :
Beijing Key Lab. of High Voltage&EMC, North China Electr. Power Univ., Beijing
fYear :
2008
fDate :
9-12 June 2008
Firstpage :
63
Lastpage :
65
Abstract :
To study the corona performance of full scale UHV DC transmission line, a 4 m long, 2 m times 2 m corona cage has been constructed. At the same time, a corona performance measuring system consists of audible noise level meter, EMI receiver and ultraviolet imaging telescope has been set up too. Audible noise level, radio interference level and total of ultraviolet photon of a 4 times 500 mm2 transmission line have been measured at different voltages. According to the test results, a method to determine the inception corona voltage of the full scale transmission line has been presented.
Keywords :
HVDC power transmission; corona; electromagnetic interference; telescopes; EMI receiver; audible noise level; audible noise level meter; corona cage; corona performance measuring system; full scale UHV DC transmission line corona performance; radiointerference level; transmission lines; ultraviolet imaging telescope; ultraviolet photon; Acoustic noise; Corona; Electromagnetic interference; Noise measurement; Optical receivers; Telescopes; Time measurement; Transmission line measurements; Transmission lines; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location :
Vancouver, BC
ISSN :
1089-084X
Print_ISBN :
978-1-4244-2091-9
Electronic_ISBN :
1089-084X
Type :
conf
DOI :
10.1109/ELINSL.2008.4570278
Filename :
4570278
Link To Document :
بازگشت