• DocumentCode
    2212381
  • Title

    Experience with Preventing External Flashovers in HVDC Converter Stations

  • Author

    McDermid, W. ; Black, T.

  • Author_Institution
    Manitoba Hydro, Winnipeg, MB
  • fYear
    2008
  • fDate
    9-12 June 2008
  • Firstpage
    81
  • Lastpage
    84
  • Abstract
    Wall bushings, apparatus bushings, transductors (DCCTs) and post insulators are vulnerable to flashover in HVDC converter stations under conditions of non-uniform (N-U) wetting, fog, etc. Experience is reported over a 30 year period in preventing external insulation flashovers through the use of booster sheds or RTV coatings.
  • Keywords
    HVDC power convertors; flashover; insulators; saturable core reactors; substation insulation; HVDC converter stations; apparatus bushings; external insulation flashovers; nonuniform wetting; post insulators; transductors; Coatings; Flashover; HVDC transmission; Inductors; Insulators; Rain; Rectifiers; Smoothing methods; Snow; Transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
  • Conference_Location
    Vancouver, BC
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-2091-9
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2008.4570283
  • Filename
    4570283