• DocumentCode
    2212524
  • Title

    Development of an UHF detection system for partial discharge measurement in transformer insulation

  • Author

    Rengarajan, S. ; Parmar, R.N. ; Bhoomaiah, A. ; Kuntia, J.S.

  • Author_Institution
    Corp. R&D Div., Bharat Heavy Electr. Ltd., Hyderabad
  • fYear
    2008
  • fDate
    9-12 June 2008
  • Firstpage
    100
  • Lastpage
    103
  • Abstract
    A test system to detect partial discharges in transformer oil insulation, using an UHF sensor has been developed. The UHF sensor is basically a duel arm Archimedean spiral antenna with a frequency response of 300 -3000 MHz. The UHF signal is amplified using an RF amplifier and analysed both in time and frequency domains. Various types of discharges have been created by means of a discharge simulator and characterised. Also, the location of a discharge site is identified by using two antennae and time of flight method.
  • Keywords
    UHF amplifiers; UHF antennas; UHF detectors; partial discharge measurement; power transformer insulation; spiral antennas; RF amplifier; UHF detection system; UHF sensor; discharge simulator; duel arm Archimedean spiral antenna; frequency 300 MHz to 3000 MHz; partial discharge measurement; transformer oil insulation; Fault location; Insulation testing; Oil insulation; Partial discharge measurement; Partial discharges; Power transformer insulation; Sensor phenomena and characterization; Sensor systems; Spirals; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
  • Conference_Location
    Vancouver, BC
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-2091-9
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2008.4570288
  • Filename