• DocumentCode
    2215571
  • Title

    Three dimensional FEM calculations on shielding of power frequency magnetic fields from a substation

  • Author

    Hasselgren, L. ; MÖller, E. ; Hamnerius, Y.

  • Author_Institution
    Dept. of Microwave Technol., Chalmers Univ. of Technol., Goteborg, Sweden
  • fYear
    1993
  • fDate
    9-13 Aug 1993
  • Firstpage
    158
  • Lastpage
    159
  • Abstract
    A 3-D finite element model is used to analyze the shielding effectiveness of an eddy-current shield applied to a 10/0.4-kV substation. The influence of the shield extension is shown. Furthermore, the insertion of a door in the shielded wall was found to create a locally elevated B-field. The results show that the magnetic field from substations can be shielded so that disturbances on VDT (video display terminal) screens in the vicinity can be avoided
  • Keywords
    eddy currents; finite element analysis; magnetic fields; magnetic shielding; substations; 0.4 kV; 10 kV; 3-D finite element model; 3D FEM; VDT screens; door; eddy-current shield; locally elevated B-field; magnetic shielding; power frequency magnetic fields; shielded wall; shielding effectiveness; substation; video display terminal; Bars; Eddy currents; Frequency; Gears; Magnetic field measurement; Magnetic shielding; Microwave technology; Substations; Switches; Vectors;