Abstract
Over the past 30 years handheld instrumentation has been developed that enables the detection of partial discharge activity with the plant in normal service. The continuing challenge in making meaningful field based partial discharge measurements is to reliably relate the severity of any detected partial discharge activity to the risk of failure of the item under test. The risk will be a function of such factors as the location within the test item, ambient conditions, materials, the severity of the activity and the history of failure (if any). This paper describes some of the field experience gained whist using this equipment and also introduces results from recent laboratory based accelerated ageing tests on 11 kV vacuum switchgear that employed cast resin insulation material where surface partial discharge activity was observed from inception to failure.
Keywords
ageing; distribution networks; life testing; partial discharge measurement; resins; risk analysis; switchgear testing; vacuum insulation; accelerated ageing tests; cast resin insulation; distribution switchgear testing; partial discharge measurements; risk analysis; vacuum switchgear; voltage 11 kV; Accelerated aging; History; Instruments; Insulation testing; Laboratories; Life estimation; Materials testing; Partial discharge measurement; Partial discharges; Switchgear;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location
Vancouver, BC
ISSN
1089-084X
Print_ISBN
978-1-4244-2091-9
Electronic_ISBN
1089-084X
Type
conf
DOI
10.1109/ELINSL.2008.4570430
Filename
4570430
Link To Document