Abstract
An optimal firing strategy for N cascaded, 6-pulse, phase-controlled power converters of a HVDC link is proposed. Minimization of the harmonic currents injected into the AC system (by both the inverters and rectifiers) is achieved through simultaneous control of the firing angles of the N power converters. With relatively low values of N (4 12-pulse, or 8 6-pulse), the resultant AC current harmonics are substantially lower than for comparable 12- or 6-pulse converters. Also, the DC voltage harmonics are greatly reduced over 12-pulse operation
Keywords
DC power transmission; optimal control; phase control; power control; power convertors; power system control; power system harmonics; power system interconnection; thyristor applications; AC current harmonics; DC voltage harmonics; HVDC link; interconnection; inverters; minimization; minimum harmonic currents; optimal firing angle control; phase control; power converters; power systems; rectifiers; simultaneous control; thyristors; Active filters; HVDC transmission; Inverters; Optimal control; Power harmonic filters; Power system harmonics; Pulse power systems; Pulse transformers; Reactive power; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics, Control, and Instrumentation, 1993. Proceedings of the IECON '93., International Conference on
Conference_Location
Maui, HI
Print_ISBN
0-7803-0891-3
Type
conf
DOI
10.1109/IECON.1993.339126
Filename
339126
Link To Document