Abstract :
Application of vacuum interruption in distribution switchgear, especially in autoreclosers, which have uniquely high demands on vacuum fault interrupters, are discussed. The fast open-close-open sequence and its associated highly asymmetrical waveforms are some of the difficulties encountered. The authors present their solution to these problems in the form of an economical axial magnetic field interrupter that realizes current densities of up to 1.68 kA/cm2-the most efficient axial magnetic interrupter that is in production today. Actual design test data per ANSI C37.60 is shown
Keywords :
distribution networks; magnetic fields; power system protection; vacuum interrupters; ANSI C37.60 standard; asymmetrical waveforms; autoreclosers; axial magnetic field interrupters; current densities; design test data; distribution switchgear; open-close-open sequence; vacuum fault interrupters; vacuum interruption; Circuit breakers; Circuit testing; Contacts; Interrupters; Magnetic fields; Magnetic switching; Power system reliability; Switches; Switchgear; Vacuum systems;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1996. Proceedings. ISDEIV., XVIIth International Symposium on
Conference_Location :
Berkeley, CA
Print_ISBN :
0-7803-2906-6
Type :
conf
DOI :
10.1109/DEIV.1996.545525
Filename :
545525
Link To Document :
بازگشت