DocumentCode
2230019
Title
Influence of harmonic injections on the performance of certain analog and digital protection and regulation equipment
Author
Nadipalli, Kalyan ; Hari, Sriharsha ; Hulse, Kelly ; Hess, Herbert L. ; Johnson, Brian K. ; Angell, David
Author_Institution
Univ. of Idaho, ID, USA
fYear
2008
fDate
28-30 Sept. 2008
Firstpage
1
Lastpage
5
Abstract
An investigation into harmonic performance of representative controllers for reclosers, voltage regulators, and capacitor banks. An appropriately rated current amplifier applies four categories of terminal voltage and currents to the devices under test: a control sequence without harmonics, a sequence of waveforms having voltage harmonics only, a sequence having current harmonics only, and a sequence having a combination of voltage and current harmonics. Electromechanical recloser control exhibits significant difficulty in detecting faults in the presence of harmonics. Digital reclosers identify the faults but show significant delay; newer model microprocessor-based relays show no significant difficulties in the presence of harmonics. Voltage regulator controls show no abnormal operation; capacitor bank control has significant difficulty. Experimental results are presented and discussed.
Keywords
capacitors; power apparatus; power system harmonics; power system protection; switchgear; voltage regulators; analog protection equipment; capacitor banks; current amplifier; current harmonics; digital protection equipment; electromechanical recloser control; harmonic injection; regulation equipment; voltage harmonics; voltage regulator; Capacitors; Delay; IEC standards; Power harmonic filters; Power system harmonics; Power system protection; Protective relaying; Regulators; Variable speed drives; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Symposium, 2008. NAPS '08. 40th North American
Conference_Location
Calgary, AB
Print_ISBN
978-1-4244-4283-6
Type
conf
DOI
10.1109/NAPS.2008.5307348
Filename
5307348
Link To Document