DocumentCode
2236793
Title
PR-controller in a 2MW grid side windpower converter
Author
Uphues, Andreas ; Nötzold, Kilian ; Wegener, Ralf ; Soter, Stefan
Author_Institution
Retostronik GmbH, Gevelsberg, Germany
fYear
2012
fDate
19-21 March 2012
Firstpage
1073
Lastpage
1078
Abstract
To regulate the current in grid connected power converters mostly proportional integral (PI) controller in synchronous reference frame are used. To improve their known drawbacks such as complexity of control structure because of the dq-transformation and the poor behavior concerning low order harmonics compensation, proportional resonant (PR) controller gained a large popularity. This paper describes the differences between using PI-controller and PR-controller in a 2MW grid connected power converter for wind turbines. The control theory of PR filters and implementing them as delta based infinite impulse response (IIR) filters in a fixed-point microcontroller is presented. The PR-controller with harmonic compensation has been tested in a 2MW power converter.
Keywords
IIR filters; PI control; electric current control; fixed point arithmetic; microcontrollers; power convertors; power grids; power harmonic filters; power system interconnection; wind turbines; PI-controller; PR controller; PR filters; control theory; current regulation; dq-transformation; fixed point microcontroller; grid connected power converter; harmonic compensation; infinite impulse response filter; power 2 MW; proportional integral controller; proportional resonant controller; synchronous reference frame; wind turbines; Harmonic analysis; ISO standards; Power harmonic filters; Power system stability; Resonant frequency; Stability analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Technology (ICIT), 2012 IEEE International Conference on
Conference_Location
Athens
Print_ISBN
978-1-4673-0340-8
Type
conf
DOI
10.1109/ICIT.2012.6210082
Filename
6210082
Link To Document