Title :
Prompt identification of weak transmission lines regarding voltage collapse
Author :
Sobierajski, M. ; Wilkosz, K. ; Bertsch, J. ; Fulczyk, M. ; Rehtanz, C.
Author_Institution :
Wroclaw Univ. of Technol., Poland
Abstract :
In this paper, a practical and simple approach for finding the weakest power transmission line in a power system is proposed to be used. This is the P-Q curve idea. One can create the P-Q curve for each transmission line. The minimal distance from the steady state point to the P-Q boundary curve may be treated as the degree of the voltage security at a given transmission line. Additionally, using the P-Q curves, one can calculate the probability of branch voltage collapse for uniformly distributed active and reactive powers.
Keywords :
power system dynamic stability; power system identification; power system security; power transmission lines; probability; transmission line theory; P-Q boundary curve; P-Q curve approach; branch voltage collapse probability; power system voltage security; steady state point; weak transmission lines identification;