DocumentCode
2245625
Title
Improvement of high voltage switchgear reliability
Author
Thuries, E. ; Ebersohl, G. ; Dupraz, J.P. ; Chetay, O. ; Moncorgé, J.P.
Author_Institution
GEC Alsthom T&D, France
fYear
1994
fDate
7-9 Nov 1994
Firstpage
145
Lastpage
149
Abstract
The reliability and availability of MV and HV circuit breakers is essential to the fulfilment of power network failure elimination. Experience has shown that about a quarter of major failures are due to failure of circuit breaker auxiliary and control circuits. Another important cause of failures is faulty SF6 density monitoring systems. The integrity of this parameter is fundamental in ensuring the apparatus´ dielectric rigidity as well as interruption of high fault currents. The last cause of major circuit breaker failures is the risk of failure of its mechanical parts. In order to solve these problems, the authors have undertaken the design of new low voltage auxiliary switchgear equipment with integrated state monitoring functions by making use of the new possibilities offered by appropriate digital equipment
Keywords
SF-6 insulation; automatic test equipment; automatic testing; electric breakdown; gas insulated switchgear; insulation testing; power engineering computing; reliability; switchgear testing; HV; SF6; availability; design; digital equipment; integrated state monitoring; power network failure; switchgear reliability; testing;
fLanguage
English
Publisher
iet
Conference_Titel
Trends in Distribution Switchgear, 1994., Fourth International Conference on
Conference_Location
London
Print_ISBN
0-85296-624-5
Type
conf
DOI
10.1049/cp:19941079
Filename
341486