DocumentCode
2245994
Title
Influence of the MIIF index on operation of multi-infeed HVDC systems
Author
Chen, Xiuyu ; Gole, A.M. ; Han, MinXiao ; Liu, Chongru
Author_Institution
Univ. of Manitoba, Winnipeg, MB, Canada
fYear
2011
fDate
3-5 Oct. 2011
Firstpage
216
Lastpage
221
Abstract
The Multi-infeed Interaction Factor (MIIF) is an important index for quantifying the interaction between the converters of a Multi-infeed (MI) HVDC transmission system. Using an analytical formulation of power flow, the impact of ac and dc side system parameters on the MIIF is analyzed. The analysis is conducted using a two-infeed HVDC test system derived from the CIGRE HVDC Benchmark model. Results show that the ac grid effective short ratios at the MI converters, length of the tie line connecting the converter ac buses, and the power flow distribution in the ac network are the main factors affecting the MIIF value. The magnitude of the voltage drop at the converter bus does not influence the MIIF value.
Keywords
HVDC power transmission; distribution networks; load flow; power grids; CIGRE HVDC benchmark; MIIF index; ac buses; ac grid; ac network; ac side system parameters; dc side system parameters; multiinfeed HVDC transmission; multiinfeed interaction factor; power flow distribution; voltage drop; Equations; HVDC transmission; Indexes; Inverters; Load flow; Mathematical model; Reactive power; HVDC transmission; Multi-Infeed Interaction Factor (MIIF); Multi-Infeed system;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Power and Energy Conference (EPEC), 2011 IEEE
Conference_Location
Winnipeg, MB
Print_ISBN
978-1-4577-0405-5
Type
conf
DOI
10.1109/EPEC.2011.6070199
Filename
6070199
Link To Document