DocumentCode :
2254524
Title :
Practical design considerations for application of GIS MV switchgear
Author :
Lav, Chun Ty Shawn ; Staley, David B. ; Olsen, T. W Ted
Author_Institution :
Siemens Power T&D Inc., Raleigh, NC, USA
fYear :
2003
fDate :
15-17 Sept. 2003
Firstpage :
93
Lastpage :
100
Abstract :
In a biotechnology facility project, the decision was made to require arc resistant medium voltage (MV) switchgear for the safety of operating personnel. The available service voltage was 26.4 kV, limiting the availability of proven designs of arc-resistant switchgear. As a result, the owner considered use of medium voltage gas insulated switchgear (GIS) with vacuum circuit breakers. Once this decision was made, consideration was given to using the same class of switchgear for the 4.16 kV voltage equipment in the facilities. This offered advantages of uniformity, commonality of spares, and simplification of operator training. This paper focuses on the rationale for selection of GIS switchgear, and the design considerations that had to be addressed as the project moved from concept to installation to operation. Among the issues discussed are: space requirements for conventional and GIS equipment; arc resistant performance of GIS equipment; design commonality between 4.16 kV and 26.4 kV equipment; installation (cable issues, foundations, workspace, etc.); environmental considerations; total cost of ownership; reliability/availability; and operational experience.
Keywords :
circuit-breaking arcs; gas insulated switchgear; personnel; safety; vacuum circuit breakers; 4.16 to 26.4 kV; GIS MV switchgear; GIS equipment; arc resistant medium voltage switchgear; arc resistant performance; availability; available service voltage; biotechnology facility project; design commonality; design considerations; environmental considerations; installation; medium voltage gas insulated switchgear; operating personnel safety; operational experience; operator training simplification; reliability; space requirements; spares commonality; total cost of ownership; uniformity; vacuum circuit breakers; Availability; Biotechnology; Circuit breakers; Gas insulation; Geographic Information Systems; Immune system; Medium voltage; Personnel; Safety; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference, 2003. Record of Conference Papers. IEEE Industry Applications Society 50th Annual
ISSN :
0090-3507
Print_ISBN :
0-7803-7956-X
Type :
conf
DOI :
10.1109/PCICON.2003.1242603
Filename :
1242603
Link To Document :
بازگشت