    Recent important changes in IEEE motor and generator winding insulation diagnostic testing standards

  • Author

    Stone, Greg C.

  • Author_Institution
    Iris Power Eng., Toronto, Ont., Canada
  • fYear
    2003
  • fDate
    15-17 Sept. 2003
  • Firstpage
    101
  • Lastpage
    110
  • Abstract
    IEEE standards and test procedures are widely used by motor and generator vendors and users to commission windings in new machines, as well as evaluate the condition of the winding insulation in operating machines. Until recent revisions, the basic procedures and standards in use were written over 25 years ago. Since the 1970s, motor windings have encountered many changes in their design and manufacture. The result was that the interpretation of results in many of the standards was no longer valid for the more modem motors. Over the past 5 years, the IEEE Power Engineering Society has conducted a major review and updating of most of these standards. Many important changes in test procedures and interpretation guidelines have resulted. This paper reviews the main insulation standards used for stator and rotor winding diagnostic testing, and discusses the changes that have been made. Standards discussed include: IEEE 43, 56, 95, 286, 522, and 1434. For example, IEEE 43-2000 now requires a minimum insulation resistance of 100 Megohms for new stator windings rated 2300 V or more, rather than the ´kV+1´ that was required in the past. Furthermore, the interpretation for polarization index has changed such that a motor with a PI of 1 is no longer automatically classed as ´bad´.
  • Keywords
    AC generators; AC motors; IEEE standards; insulation testing; machine insulation; machine testing; partial discharge measurement; power factor; rotors; stators; surges; AC Hipot testing; DC Hipot testing; IEEE 1434; IEEE 286; IEEE 522; IEEE 56; IEEE 95; IEEE Power Engineering Society; IEEE standards; IEEE test procedures; generator winding insulation diagnostic testing; insulation standards; motor winding insulation diagnostic testing; partial discharge testing; polarization index; power factor tip-up test; rotor winding diagnostic testing; stator winding diagnostic testing; surge tests; windings commissioning; Aging; Automatic testing; Dielectrics and electrical insulation; Insulation testing; Machine windings; Manufacturing; Materials testing; Polarization; Power & Energy Society; Stator windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 2003. Record of Conference Papers. IEEE Industry Applications Society 50th Annual
  • ISSN
    0090-3507
  • Print_ISBN
    0-7803-7956-X
  • Type

    conf

  • DOI
    10.1109/PCICON.2003.1242604
  • Filename
    1242604