• DocumentCode
    2255974
  • Title

    The influence of cable capacitance, generator neutral grounding and zig-zag transformer to third harmonic produced by synchronous generator

  • Author

    Abdullah, Mohd Faris ; Hamid, Nor Hisham ; Baharudin, Z. ; Razak, M.H.S.A. ; Hisham, I.B.

  • Author_Institution
    Electr. & Electron. Eng. Dept., Univ. Teknol. PETRONAS, Tronoh, Malaysia
  • fYear
    2012
  • fDate
    12-14 Dec. 2012
  • Firstpage
    380
  • Lastpage
    385
  • Abstract
    Salient pole synchronous generator is one of harmonic sources that causes various power system harmonic problem especially related to neutral. This paper aims to study the characteristics of third harmonic voltage and current from generator when connected to balanced load via cable, generator load connection with different generator neutral grounding resistor and generator load connection shunted by zig-zag transformer. Lab scale experiments have been conducted to vary all parameters related to cable capacitor and generator neutral grounding resistor under various combined resistive and inductive load. Cable capacitance which depends on cable length, size and number of parallel cable, combined with load impedance determines the third harmonic current magnitude. The presence of cable capacitance that interact with generator inductance resulted to series harmonic resonance at 9th and 15th harmonic order that causes high 9th and 15th harmonic current flowing between generator and cable capacitor. Generator neutral grounding resistor can effectively reduce the third harmonic in the phase and neutral. However care should be taken not to use very high generator neutral grounding resistor that can also restrict earth fault current that may pose problem to the sensitivity of earth fault protection system. Zig-zag transformer efficiently divert third harmonic current from generator to enter the load but high circulating third harmonic current between generator and zig-zag transformer may pose heating problem to the equipments.
  • Keywords
    earthing; power system harmonics; power transformers; resistors; synchronous generators; cable capacitance; generator load connection; generator neutral grounding; grounding resistor; harmonic sources; inductive load; load impedance; power system harmonic; resistive load; salient pole synchronous generator; third harmonic voltage; zig-zag transformer; Third harmonic voltage; cable capacitance; grounding; synchronous generator; third harmonic current;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    IPEC, 2012 Conference on Power & Energy
  • Conference_Location
    Ho Chi Minh City
  • Type

    conf

  • DOI
    10.1109/ASSCC.2012.6523297
  • Filename
    6523297