• DocumentCode
    2259212
  • Title

    The effect of threshold voltage of PD sensors on RPDIV and RPDEV of twisted-pair samples

  • Author

    Kimura, K. ; Matsumura, Takeshi

  • Author_Institution
    Nara Nat. Coll. of Technol., Nara, Japan
  • fYear
    2011
  • fDate
    6-10 Sept. 2011
  • Firstpage
    128
  • Lastpage
    131
  • Abstract
    Using a newly developed PD measuring system with RFCT and horn antenna under repetitive voltage impulses, RPDIV and RPDEV of twisted-pair were obtained according to the definition of IEC61934Ed.2.0. Weibull distribution of hundred RPDIV and RPDEV shows that PRDIV is always higher than RPDEV for both PD sensors and that the difference was less than 5% of RPDIV. The difference of sensitivity of PD sensors was discussed with threshold voltage for the calculation of RPDIV and RPDEV. Recalculation shows the linear dependence of threshold voltage on RPDIV and RPDEV.
  • Keywords
    current transformers; electric sensing devices; horn antennas; partial discharge measurement; IEC61934Ed.2.0; Weibull distribution; horn antenna; linear dependence; partial discharge sensors; radio frequency current transformer; repetitive PD extinction voltage; repetitive PD inception voltage; repetitive voltage impulses; sensitivity; threshold voltage; twisted-pair samples; Antenna measurements; Horn antennas; Noise measurement; Partial discharges; Sensors; Threshold voltage; Voltage measurement; IEC; RPDEV; RPDIV; partial discharges; repetitive impulse; sensors; threshold;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials (ISEIM), Proceedings of 2011 International Conference on
  • Conference_Location
    Kyoto
  • Print_ISBN
    978-4-88686-074-3
  • Type

    conf

  • DOI
    10.1109/ISEIM.2011.6826366
  • Filename