Fault simulation studies of single-line faults in a delta-delta connected distribution system
Author
Momoh, J.A. ; Dias, L.G. ; Thor, T. ; Laird, D.N.
Author_Institution
Dept. of Electr. Eng., Howard Univ., Washington, DC, USA
fYear
1993
fDate
16-18 Aug 1993
Firstpage
377
Abstract
Single-line faults in delta-delta connected distribution systems normally draw very low fault currents and cannot be detected by the usual overcurrent protective devices. The ground alarm relays that are used in this type of system can detect most ground faults but can neither identify the faulty feeder nor classify the fault type, nor detect open conductor faults. This paper describes an exhaustive simulation study, which will provide criteria for the detection and identification of single-line faults in a delta-delta connected distribution system. The conclusion is, that for single-line faults with no intermittent contact, criteria can be obtained, which can be used for detection and identification of single-line faults (including open conductor faults)
Keywords
digital simulation; distribution networks; electrical faults; identification; combined faults; delta-delta connected distribution system; fault currents; fault simulation; ground alarm relays; ground faults; open conductor faults; overcurrent protective devices; series fault; shunt fault; single-line faults; Capacitance; Conductors; Electrical fault detection; Fault currents; Fault detection; Fault diagnosis; Impedance; Power system faults; Power system protection; Protective relaying;
fLanguage
English
Publisher
ieee
Conference_Titel
Circuits and Systems, 1993., Proceedings of the 36th Midwest Symposium on
Conference_Location
Detroit, MI
Print_ISBN
0-7803-1760-2
Type
conf
DOI
10.1109/MWSCAS.1993.343031
Filename
343031
Link To Document