• DocumentCode
    226457
  • Title

    Effect of dead times on the values of input current harmonics drawn from the grid by a voltage-source active rectifier

  • Author

    Kus, Vaclav ; Josefova, Tereza

  • Author_Institution
    Dept. of Electromech. & Power Electron., Univ. of West Bohemia, Pilsen, Czech Republic
  • fYear
    2014
  • fDate
    9-10 Sept. 2014
  • Firstpage
    165
  • Lastpage
    168
  • Abstract
    This paper presents an effect of dead times on values of an input current harmonics drawn from an electric grid by a voltage-source active rectifier. The first part shows a derivation of the effect on one pulse of the voltage and then the values of the current harmonics are derived. The main section discusses a description of voltage with the pulse width modulation with respect to the dead time. A voltage waveform at the input terminals of the inverter, its harmonic analysis, and calculations of the current harmonics values are derived. The last part shows simulations and comparison of the harmonic analysis of the current with and without dead times.
  • Keywords
    harmonic analysis; power system harmonics; rectifiers; dead times; harmonic analysis; input current harmonics; pulse width modulation; voltage-source active rectifier; Analytical models; Harmonic analysis; Mathematical model; Power harmonic filters; Pulse width modulation; Rectifiers; Switching frequency; current harmonics; dead time; frequency analysis; pulse width modulation; voltage-source active rectifier;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Electronics (AE), 2014 International Conference on
  • Conference_Location
    Pilsen
  • ISSN
    1803-7232
  • Print_ISBN
    978-8-0261-0276-2
  • Type

    conf

  • DOI
    10.1109/AE.2014.7011692
  • Filename
    7011692