DocumentCode
2267997
Title
An improved measurement placement method against loss of multiple measurements and branches
Author
Ding, Qifeng ; Abur, Ali
Author_Institution
Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
Volume
1
fYear
2002
fDate
2002
Firstpage
234
Abstract
A meter placement method that ensures network observability in case of a loss of a single measurement or a branch outage, has been presented earlier (see F.H. Magnago et al., IEEE Trans. Power Syst., vol15, 2000). This paper extends the results of the previous work and develops an improved method which can place meters in a way that will maintain full observability even when a group of measurements or branches are eliminated from the system. The method is described in detail along with a numerical example which illustrates its application.
Keywords
integer programming; observability; power meters; power system measurement; power system state estimation; branch outage; integer programming; loss of multiple branches; loss of multiple measurements; loss of single measurement; measurement placement method; network observability; power system state estimation; Energy management; Linear programming; Loss measurement; Observability; Power system modeling; Real time systems; Robustness; State estimation; Substations; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2002. IEEE
Print_ISBN
0-7803-7322-7
Type
conf
DOI
10.1109/PESW.2002.984991
Filename
984991