Abstract :
In order to prove the electrical, thermal and mechanical layout of directly buried gas-insulated transmission lines (GIL), a long term test was carried out at the test field of IPH in Berlin, Germany. A single phase was buried and subjected to the cycles of higher current of 4000 A and higher operation voltage of 480 kV to simulate 50 years of life time. Electrical, thermal and mechanical measurements have been carried out and compared with the numerical simulation. In this article some comparisons of measured and calculated values are presented.
Keywords :
SF6 insulation; gas mixtures; insulation testing; life testing; nitrogen; power cable insulation; power cable testing; power transmission lines; underground cables; 4000 A; 480 kV; 50 year; Germany; N2-SF6; N2/SF6 gas mixture; buried gas-insulated transmission lines; electrical layout; electrical measurements; long-term testing; mechanical layout; mechanical measurements; numerical simulation; thermal layout; thermal measurements; underground power cables; Aluminum; Conductors; Gas insulated transmission lines; Gas insulation; Heating; Power transmission; Sulfur hexafluoride; Testing; Transmission line measurements; Voltage;
Conference_Titel :
Power Engineering Society Winter Meeting, 2002. IEEE
Print_ISBN :
0-7803-7322-7
DOI :
10.1109/PESW.2002.985232