The effect of the distance between transformer and MV arresters on the surges transferred to the LV side
Author
Piantini, A. ; de Carvalho, T.O. ; Obase, P.F. ; Janiszewski, J.M. ; Santos, G.J.G. ; Fagundes, D.R. ; Uchoa, J.I.L. ; Kunz, E.N.
Author_Institution
Inst. of Electrotechnics & Energy, Univ. of Sao Paulo, Sao Paulo, Brazil
fYear
2012
fDate
17-20 Sept. 2012
Firstpage
105
Lastpage
109
Abstract
The western part of the state of Rio Grande do Sul, in South Brazil, is characterized by high ground flash densities. In the period 2003-2011, lightning overvoltages accounted for about 47 % of the total number of distribution transformer failures observed in the service area of the power company AES Sul. This paper presents the results of an investigation on the influence of the distance between transformer and medium voltage arresters on the surges transferred to the secondary side. The analysis, performed through simulations using the Alternative Transients Program (ATP), shows that in general higher voltages are produced by subsequent strokes. Although the amplitudes of the voltages transferred to the secondary side tend to increase as the surge arrester approaches the transformer, the distance between these equipment should be as short as possible.
Keywords
arresters; power transformers; ATP; LV side; MV arresters; Rio Grande do Sul; alternative transients program; distribution transformer failures; high ground flash densities; medium voltage arresters; power company AES Sul; secondary side; service area; surge arrester; Arresters; Insulators; Lightning; Power transformer insulation; Surges; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location
Shanghai
Print_ISBN
978-1-4673-4747-1
Type
conf
DOI
10.1109/ICHVE.2012.6357064
Filename
6357064
Link To Document