DocumentCode :
2277125
Title :
Analysis of axial magnetic field in vacuum interrupters of large current vacuum circuit breaker with dual-contact
Author :
Yu, Li ; Li, Feng ; Bao-jie, Qiu ; Yuan, Shun
Author_Institution :
Dept. of Electr. Eng., Shenyang Inst. of Eng., Shenyang, China
fYear :
2011
fDate :
20-23 Aug. 2011
Firstpage :
1
Lastpage :
4
Abstract :
A new type of “dual-contact” structure of vacuum interrupter is proposed in the paper. It consists of main contact and arc contact, which are used to break short circuit current and carry rated current, respectively. Using double-bellows, the contact bounce can be substantially reduced. In order to increase short circuit current breaking capacity of large-current vacuum interrupter, an optimal design of “iron magnetic ring” is put into arc contact to improve its magnetic performance. In terms of the new type large current vacuum interrupter, simulation results show that it is excellent in axial magnetic density and radial magnetic uniformity at current peak, and the contact area is effectively utilized.
Keywords :
vacuum circuit breakers; vacuum interrupters; arc contact; axial magnetic density; axial magnetic field; current peak; dual contact; iron magnetic ring; large current vacuum circuit breaker; large current vacuum interrupter; radial magnetic uniformity; short circuit current breaking capacity; vacuum interrupters; Circuit breakers; Interrupters; Magnetic cores; Magnetic fields; Magnetic flux density; Vacuum arcs;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4577-1044-5
Type :
conf
DOI :
10.1109/ICEMS.2011.6073628
Filename :
6073628
Link To Document :
بازگشت