DocumentCode :
2277389
Title :
Precision measurement of harmonic current and power at industrial frequency
Author :
Lu Zuliang ; Wang Lei ; Li Min ; Liu Lijuan ; Zhou Hao
Author_Institution :
Nat. Inst. of Metrol., Beijing
fYear :
2008
fDate :
8-13 June 2008
Firstpage :
204
Lastpage :
205
Abstract :
The precision measurement for harmonic current and power up to 60th order and some validating experiments is reported. The uncertainty of harmonics current reference to fundamental is less than 36 muA/A (k=2) for range up to 50 A. The uncertainty of harmonic power reference to the fundamental apparent power is less than 42 muW/VA (k=2) for voltage and current range up to 500 V and 50 A.
Keywords :
electric current measurement; measurement standards; power measurement; harmonic current measurement; harmonic power measurement; harmonic power reference; harmonic power standard; harmonics current reference; industrial frequency; Circuit noise; Current measurement; Frequency measurement; Metrology; Power measurement; Power system harmonics; Signal design; Signal resolution; Uncertainty; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements Digest, 2008. CPEM 2008. Conference on
Conference_Location :
Broomfield, CO
Print_ISBN :
978-1-4244-2399-6
Electronic_ISBN :
978-1-4244-2400-9
Type :
conf
DOI :
10.1109/CPEM.2008.4574724
Filename :
4574724
Link To Document :
بازگشت