• DocumentCode
    2277389
  • Title

    Precision measurement of harmonic current and power at industrial frequency

  • Author

    Lu Zuliang ; Wang Lei ; Li Min ; Liu Lijuan ; Zhou Hao

  • Author_Institution
    Nat. Inst. of Metrol., Beijing
  • fYear
    2008
  • fDate
    8-13 June 2008
  • Firstpage
    204
  • Lastpage
    205
  • Abstract
    The precision measurement for harmonic current and power up to 60th order and some validating experiments is reported. The uncertainty of harmonics current reference to fundamental is less than 36 muA/A (k=2) for range up to 50 A. The uncertainty of harmonic power reference to the fundamental apparent power is less than 42 muW/VA (k=2) for voltage and current range up to 500 V and 50 A.
  • Keywords
    electric current measurement; measurement standards; power measurement; harmonic current measurement; harmonic power measurement; harmonic power reference; harmonic power standard; harmonics current reference; industrial frequency; Circuit noise; Current measurement; Frequency measurement; Metrology; Power measurement; Power system harmonics; Signal design; Signal resolution; Uncertainty; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements Digest, 2008. CPEM 2008. Conference on
  • Conference_Location
    Broomfield, CO
  • Print_ISBN
    978-1-4244-2399-6
  • Electronic_ISBN
    978-1-4244-2400-9
  • Type

    conf

  • DOI
    10.1109/CPEM.2008.4574724
  • Filename
    4574724