• DocumentCode
    2277947
  • Title

    Fault location and type identification on transmission line using a novel traveling wave method

  • Author

    Jianyin Liu ; Zhong Zheng

  • Author_Institution
    State Key Lab. for Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
  • fYear
    2012
  • fDate
    17-20 Sept. 2012
  • Firstpage
    290
  • Lastpage
    293
  • Abstract
    This paper described the principle of transmission line fault location based on traveling waves. The uncertainty of wave speed brings error to fault location based on traveling waves. The present fault location methods avoiding wave speed were based on single or double terminal traveling waves. However, invalidation or great error will occur when the attenuated waves can not be measured after refraction or reflection. The authors introduced two novel and easy-to-measure parameters, which provide a new approach to greatly improve the accuracy of fault location. The first pulse wave of fault also gives many characteristic information of the failure which was used to identify the type of failures to convenient the workers making targeted rush repair. Field measurement and calculation results are compared and the related limitations are discussed.
  • Keywords
    electric field measurement; fault diagnosis; fault location; power transmission faults; power transmission lines; power transmission protection; fault type identification; field measurement; pulse wave; terminal traveling wave; transmission line fault location; traveling wave uncertainty; Fault location; Grounding; Monitoring; Poles and towers; Power transmission lines; Transmission line measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2012 International Conference on
  • Conference_Location
    Shanghai
  • Print_ISBN
    978-1-4673-4747-1
  • Type

    conf

  • DOI
    10.1109/ICHVE.2012.6357109
  • Filename
    6357109