DocumentCode :
227854
Title :
Experimental characterization of pressure drop in a server rack
Author :
Alkharabsheh, S. ; Sammakia, B. ; Murray, Brian ; Shrivastava, S. ; Schmidt, R.
Author_Institution :
State Univ. of New York at Binghamton, Binghamton, NY, USA
fYear :
2014
fDate :
27-30 May 2014
Firstpage :
547
Lastpage :
556
Abstract :
This paper evaluates the impact of pressure drop in server racks on the cooling of the IT equipment. The measured impedance curves for servers internal resistance, rack doors, and Cable Management Arms (CMA) are used to estimate the reduction in the cooling airflow rate. In this study, 1 RU and 2 RU servers, and a 9 RU server simulator are used as representative IT equipment. A Computational Fluid Dynamics (CFD) model is used to investigate the influence of the rack structure on the thermal field. The effect of the cooling air flow rate on the temperature of the server´s internal components is also studied experimentally.
Keywords :
computational fluid dynamics; computer centres; cooling; network servers; CFD model; IT equipment cooling; cable management arms; computational fluid dynamics model; pressure drop; rack doors; server rack; servers internal resistance; Atmospheric modeling; Fans; Impedance; Resistance; Servers; Temperature measurement; CFD; Data center; cable management arm; perforated doors; pressure drop; rack structure; server resistance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on
Conference_Location :
Orlando, FL
ISSN :
1087-9870
Type :
conf
DOI :
10.1109/ITHERM.2014.6892329
Filename :
6892329
Link To Document :
بازگشت