Title :
On-site calibration of a current transformer using a Rogowski coil
Author :
Suomalainen, E.P. ; Hallstrom, J.
Author_Institution :
Helsinki Univ. of Technol. (MIKES-TKK), Helsinki
Abstract :
This paper describes an outdoor calibration of an instrument current transformer connected to 400 kV transmission line. The method of generation of the high current and the accuracy of calibration are discussed. The reference current measuring system consists of a current shunt, a Rogowski coil, two digitizing voltmeters and a computer to control voltmeters. The Rogowski coil is calibrated on-site with the current shunt. The output voltage of the Rogowski coil is not integrated, but it is scaled according to the on-site calibration result. Estimated uncertainties for ratio and phase displacement are less than 0,01% and 100 murad, respectively.
Keywords :
calibration; coils; current transformers; electric current measurement; power transmission lines; voltmeters; Rogowski coil; current shunt; current transformer; digitizing voltmeters; onsite calibration; reference current measuring system; transmission line; voltage 400 kV; Calibration; Coils; Control systems; Current measurement; Current transformers; Instruments; Phase estimation; Transmission line measurements; Voltage; Voltmeters;
Conference_Titel :
Precision Electromagnetic Measurements Digest, 2008. CPEM 2008. Conference on
Conference_Location :
Broomfield, CO
Print_ISBN :
978-1-4244-2399-6
Electronic_ISBN :
978-1-4244-2400-9
DOI :
10.1109/CPEM.2008.4574856