DocumentCode :
2280014
Title :
Novel islanding detection method for distributed generation
Author :
Lee, Hye Yeon ; Han, Byung Moon ; Cha, Han Ju
Author_Institution :
Myongji Univ., Yongin, South Korea
fYear :
2009
fDate :
20-24 Sept. 2009
Firstpage :
3378
Lastpage :
3384
Abstract :
This paper describes the development of a novel islanding detection method for inverter-based distributed generation, which uses the signal cross-correlation scheme between the injected reactive current and the power frequency deviation. The existing method injects the 5% reactive current to the rated current for detecting the frequency deviation, which brings about reduction of power quality. On the contrary, the proposed method injects the 1% reactive current to the rated current which brings about negligible degradation of power quality. The proposed method detects the islanding state by calculating the cross-correlation index between the injected reactive current and the frequency deviation. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software and experimental works with a 3 kVA hardware prototype. The proposed method can detect the islanding state effectively without degrading the power quality at the point of common connection point.
Keywords :
distributed power generation; invertors; power supply quality; PSCAD/EMTDC software simulation; apparent power 3 kVA; inverter-based distributed generation; islanding detection method; power frequency deviation; power quality; signal cross-correlation scheme; Active Method; Cross-correlation; DSP (Digital Signal Processor); Inverter-Based DG (Distributed Generation); Islanding detection; NDZ (Non-Detection Zone); Reactive Current Injection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE
Conference_Location :
San Jose, CA
Print_ISBN :
978-1-4244-2893-9
Electronic_ISBN :
978-1-4244-2893-9
Type :
conf
DOI :
10.1109/ECCE.2009.5316387
Filename :
5316387