• DocumentCode
    2281874
  • Title

    Limitation of transmission line switching overvoltages

  • Author

    Seyedi, Heresh ; Golabi, Smko ; Abam, Zaher

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Tabriz, Tabriz, Iran
  • fYear
    2010
  • fDate
    Nov. 29 2010-Dec. 1 2010
  • Firstpage
    363
  • Lastpage
    368
  • Abstract
    In this paper switching overvoltages of an actual transmission line are studied. Simulations are executed using Electro Magnetic Transients Program. A comprehensive switching transient study is performed for the Azerbaijan province network in Iran. The purpose of this study is to determine the unnecessary pre-insertion resistors in the UHV network, since the new policy is to use pre-insertion resistors only when crucial. Among the case studies presented in this work, in one case pre-insertion resistor is not necessary. Also in other cases, it is possible to omit pre-insertion resistors, with the aid of some enhancement in the insulation withstand level.
  • Keywords
    EMTP; insulation; overvoltage protection; power transmission lines; resistors; switching transients; UHV network; electro magnetic transients program; insulation; switching overvoltages; switching transient; transmission line; unnecessary pre-insertion resistors; Switching overvoltages; pre-insertion resistor; temporary overvoltages; transmission line switching;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy (PECon), 2010 IEEE International Conference on
  • Conference_Location
    Kuala Lumpur
  • Print_ISBN
    978-1-4244-8947-3
  • Type

    conf

  • DOI
    10.1109/PECON.2010.5697610
  • Filename
    5697610