Analysis and improvement of the biased stator earth fault 100% protection
Author :
Qixue, Zhang ; Xiaodong, Xia ; Jiasheng, Chen ; Jun, Chen ; Guang, Wang ; Zigang, Guo ; Xicai, Zhao
Author_Institution :
Nanjing NARI-Relays Electr. Co., Ltd., Nanjing, China
Abstract :
A kind of high resistance grounding methods of generators is few applied by a 3-phase displacement transformer, which is called Pohl (or Bütow) transformer. The secondary asymmetry of the Pohl transformer yields a fundamental zero-sequence displacement voltage so that the biased stator earth fault (SEF) 100% protection can be applied. The law of the fundamental zero-sequence voltage variation under the normal and SEF conditions is derived from an equivalent circuit. For protecting 100% stator windings, the grounding resistance should be not great than √3 times of the capacitive impedance. The characteristic surface of the biased SEF relay is analyzed, and a novel calculating method of the operational voltage via the generator voltage and frequency compensation is proposed. The miss operation zone in the low voltage and low frequency could be reduced by the improved scheme.
Keywords :
compensation; earthing; equivalent circuits; fault diagnosis; power transformer protection; relay protection; stators; synchronous generators; 3-phase displacement transformer; Pohl transformer; SEF relay; biased stator earth fault protection; electric generator; equivalent circuit; frequency compensation; resistance grounding methods; windings; zero sequence displacement voltage; zero sequence voltage variation; Circuit faults; Generators; Grounding; Relays; Stator windings; Voltage measurement; Windings; Fundamental Zero-sequence Voltage; Neutral Voltage Displacement; Pohl (or Bütow) Transformer; Stator Earth Fault Protection; Synchronous Generator;
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4577-1044-5
DOI :
10.1109/ICEMS.2011.6073934