Testing of contactors under voltage sag and non-sinusoidal voltage conditions
Author :
Hardi, Surya ; Daut, I. ; Irwanto, M.
Author_Institution :
Lab. of Electr. Energy & Ind. Electron. Syst. Cluster Res., UniMAP, Kangar, Malaysia
fYear :
2010
fDate :
Nov. 29 2010-Dec. 1 2010
Firstpage :
683
Lastpage :
688
Abstract :
Sensitivity of electromagnetic contactors for voltage sags and non-sinusoidal voltage supply has been carried out by laboratory testing. Effects of sag characteristics such as; sag magnitude, sag duration and point on wave of sag initiation to be considered on contactors behavior. Contactors are subjected to voltage sags of depth varying, sag duration varying 5 ms to 600 ms, different point on wave and under different non-sinusoidal conditions. A Schaffner Profline 2100 EMC has been used as sag generator to create sag characteristics. The results show that sensitivity curves of the contactors depend on sag magnitude, sag duration and point on wave, whereas influence of non-sinusoidal voltage is slightly different.
Keywords :
contactors; electromagnetic compatibility; power supply quality; sensitivity; Schaffner Profline 2100 EMC; electromagnetic contactor testing; nonsinusoidal voltage supply; sag duration; sag generator; sag magnitude; sensitivity curve; voltage sag; Contactors; Non-sinusoidal supply; Point on wave; Sensitive curve; Voltage sag;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy (PECon), 2010 IEEE International Conference on
Conference_Location :
Kuala Lumpur
Print_ISBN :
978-1-4244-8947-3
Type :
conf
DOI :
10.1109/PECON.2010.5697667
Filename :
5697667
Link To Document :
بازگشت