DocumentCode
2283573
Title
Voltage distortion of rotary UPS and standby engine generator sets
Author
Kusko, A. ; Peeran, S.M.
Author_Institution
Failure Anal. Associates Inc., Westborough, MA, USA
fYear
1990
fDate
7-12 Oct. 1990
Firstpage
1757
Abstract
Methods for calculating the voltage distortion produced by nonlinear loads, and design concepts for reducing the distortion are described. The impact of reducing saliency in the rotor construction and in the damper windings on the impedance of the generator to harmonic currents is analyzed. It is shown that generator voltage distortion under nonlinear loads can be controlled by either one of two methods, overrating the generator to make the nonlinear load a smaller percentage of the generator rating, or reducing the internal impedance of the generator to the harmonics of the nonlinear load current.<>
Keywords
electric distortion; standby generators; uninterruptible power supplies; damper windings; internal impedance; nonlinear loads; overrating; rotary UPS; rotor construction; standby engine generator sets; uninterruptible power supplies; voltage distortion; Damping; Engines; Harmonic analysis; Harmonic distortion; Impedance; Rotors; Shock absorbers; Standby generators; Uninterruptible power systems; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting, 1990., Conference Record of the 1990 IEEE
Conference_Location
Seattle, WA, USA
Print_ISBN
0-87942-553-9
Type
conf
DOI
10.1109/IAS.1990.152423
Filename
152423