    Voltage distortion of rotary UPS and standby engine generator sets

  • Author

    Kusko, A. ; Peeran, S.M.

  • Author_Institution
    Failure Anal. Associates Inc., Westborough, MA, USA
  • fYear
    1990
  • fDate
    7-12 Oct. 1990
  • Firstpage
    1757
  • Abstract
    Methods for calculating the voltage distortion produced by nonlinear loads, and design concepts for reducing the distortion are described. The impact of reducing saliency in the rotor construction and in the damper windings on the impedance of the generator to harmonic currents is analyzed. It is shown that generator voltage distortion under nonlinear loads can be controlled by either one of two methods, overrating the generator to make the nonlinear load a smaller percentage of the generator rating, or reducing the internal impedance of the generator to the harmonics of the nonlinear load current.<>
  • Keywords
    electric distortion; standby generators; uninterruptible power supplies; damper windings; internal impedance; nonlinear loads; overrating; rotary UPS; rotor construction; standby engine generator sets; uninterruptible power supplies; voltage distortion; Damping; Engines; Harmonic analysis; Harmonic distortion; Impedance; Rotors; Shock absorbers; Standby generators; Uninterruptible power systems; Voltage;