• DocumentCode
    2283970
  • Title

    The analysis and computation of transformer winding short-circuit current and strength on permanent fault after reclosing

  • Author

    Li, Yan ; Sun, Xin ; Li, Jian ; Zhou, Wei ; Li, Dougxue

  • Author_Institution
    Res. Instn. of Special Electr. Machines, Shenyang Univ. of Technol., Shenyang, China
  • fYear
    2011
  • fDate
    20-23 Aug. 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper has analyzed the change of power transformer short-circuit current after reclosing when a permanent faults has occurred on system. The transient process of winding flux and inrush current has been analyzed, and the different of current between initial short-circuit and reclosing can be given. The simulation results of inrush current after reclosing has been given through matlab simulation, it can be as a known condition to calculate winding electromagnetic force, and the winding strength will be checked finally. It has some significance to guide project design.
  • Keywords
    electromagnetic forces; power system transients; power transformers; short-circuit currents; transformer windings; Matlab simulation; inrush current transient process; permanent fault; power transformer short-circuit current; reclosing; transformer winding short-circuit current analysis; transformer winding short-circuit strength analysis; winding electromagnetic force; winding flux transient process; Electromagnetic forces; Fault tolerance; Power generation; Power transformers; Transformers; Windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems (ICEMS), 2011 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4577-1044-5
  • Type

    conf

  • DOI
    10.1109/ICEMS.2011.6074004
  • Filename
    6074004