DocumentCode :
2284365
Title :
Improvement of measurement techniques in PD pulse detection in large HV equipment
Author :
Zhu, H. ; Kemp, I.J.
Author_Institution :
Glasgow Caledonian Univ., UK
fYear :
1996
fDate :
23-26 Sep 1996
Firstpage :
334
Lastpage :
337
Abstract :
Partial discharge (PD) measurement has been used as a tool to assess insulation integrity for many years. In terms of detection of PD pulses, a proper assessment of insulation integrity relies on accurate acquisition of the PD pulse signal. However, measurement errors may arise due to the measurement facilities involved. This paper discusses one aspect of the measurement system, the role of connecting cables. It is shown that the connecting cables used in PD measurement may distort PD waveforms recorded. Attenuation, reflection, resonance, and coupling occur in coaxial cables for transmission of RF/UHF signals
Keywords :
insulation testing; HV equipment; PD pulse detection; connecting cable; insulation integrity; partial discharge measurement;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Dielectric Materials, Measurements and Applications, Seventh International Conference on (Conf. Publ. No. 430)